MSD / MSD-W

MSD / MSD-W

Multi compartment smoke control damper

MSD - Multi compartment smoke control damper allows usage in smoke control ducting systems.

Properties

Square dampers from 160 × 180 mm to 1500 x 800 mm
Round dampers from ø180 to 630 mm
CE certified acc. to EN 12101-8
Tested in accordance with EN 1366-10
Classified acc. to EN 13501-4
Fire resistance up to EI 120 S, activation AA, HOT 400/30
Cycling acc. to EN 12101-8:
MSD square dampers - Cmod MSD
MSD-W round dampers - C10000
MSD-W square dampers - C10000 (tested without load acc. to EN 1366-10)
External Casing leakage class ATC 3, Internal leakage class 2 acc. to EN 1751
Damper actuating by electrical actuator
Max. air speed in the system of 15 m/s, allowed pressure up to 500 Pa, or underpressure up to -1500 Pa

Specifications

Multi smoke dampers are shutters in the smoke exhaust duct systems. The dampers are designed to remove heat and combustible products (e.g. smoke) from effected fire compartments. In the event of fire the Smoke and Fire ventilation system opens the damper in the affected section and removes combustion products and heat from this section. The damper blade is controlled by electrical actuating mechanism. Dampers are fire resistant and are intended for systems with automatic activation. Dampers can be installed in construction of the fire compartment.Basic types of dampers:MSD Cycling test with load (possible design .44, .54)MSD-W Cycling test without load (possible design .44, .54, .4M0, .4M1, .5M0 and .5M1)Dampers MSD can be open against flow and pressure.Dampers MSD-W has to be open with the help of flow or without flow present.