SEDM

SEDM

Multi compartment smoke control damper

SEDM - Multi compartment smoke control damper allows usage in smoke control ducting systems. Suitable for heat and smoke extraction from several comparements at the same time.

Properties

Square dampers from 180 × 180 mm to 1600 x 1000 mm
CE certified acc. to EN 12101-8
Tested in accordance with EN 1366-10
Classified acc. to EN 13501-4
Fire resistance up to EI 120 S, activation AA/MA, HOT 400/30
Cycling test in class Cmod acc. to EN 12101-8
External Casing leakage class ATC 3, Internal leakage class 2 acc. to EN 1751
Damper actuating by electrical actuator
Max. air speed in the system of 15 m/s, allowed pressure up to 500Pa, or underpressure up to -1500 Pa

Specifications

Smoke extraction dampers - multi are shutters in the smoke exhaust piping systems. The dampers are designed to remove heat and combustible products (e.g. smoke) from effected fire compartments. In the event of fire the Smoke and Fire ventilation system opens the damper in the affected section and removes combustion products and heat from this section. The damper blade is controlled by electrical actuating mechanism. Dampers are fire resistant and are intended for systems with manual or automatic activation. Dampers are designed for using in fire compartments that can be connected to the smoke exhaust ducts (tested according to EN 1366-8) or they can be installed in or on the construction of the fire compartment. Dampers can be delivered with or without flanges.