SEDM-2D

SEDM-2D

Multi compartment smoke control damper

SEDM-2D are intended to be used in multi compartment smoke control systems in vertical duct (shaft) installations.

Properties

Dimensions width B x height H: from 350x300 mm up to 1105 x 1105 mm by 5 mm
Total depth of 90 mm (built-in depth 80 mm) without grille
Grilles of 77% to 95% effective cross section available
Opening and securing within 5 seconds
CE certification according to EN 12101-8
Tested according to EN 1366-10
Classified according to 13501-4
Pressure class 3 (underpressure 1500 Pa / overpressure 500 Pa)
Closed blade tightness class 3 according to EN 1751
In accordance with NF 61.937-1 and NF 61.937-10
Main advantages
Zero power consumption in stand-by position
Instant opening and fast closing
Small built-in dimensions
Light design of high fire and pressure resistance
Large effective area
Room protected from moving parts
Wide range of damper dimensions
Easy installation also into thin shaftwall materials
Availability of spare parts

Specifications

Smoke control dampers SEDM-2D (hereinafter named also simply as „the dampers“) are intended to be used in multi compartment smoke control systems in vertical duct (shaft) installations. In normal situation, the dampers remain closed (stand-by position). Upon an activation signal emitted either in the event of a fire, or during a functional test, the dampers of given compartments open in order to allow smoke and heat from the fire to be extracted outside the building. SEDM-2D dampers open to the inside of the duct. The dampers opened during functional testing may be put back to the stand-by (closed) position by hand. The dampers consist of a two calcium-silicate blade reinforced by steel crossbeams hanged on spring-equipped hinges, combined calcium-silicate and galvanized steel body, a cold seal (silicon gasket) and a carbon based thermo-expanded hot seal, electrically activated restraint mechanism equipped by a permanent magnet with an electric coil, optional with end switches, and a metallic grille. The dampers may be installed to the shaft directly using fire-resistant mastic, or using an optional installation frame.